28 Chapter 4 Documentation Number UD128A8D4602 Manual
B&B Electronics Mfg Co – 707 Dayton Rd - PO Box 1040 - Ottawa IL 61350 - Ph 815-433-5100 - Fax 815-433-5104
B&B Electronics Ltd – Westlink Comm. Pk. – Oranmore, Galway, Ireland – Ph 353-91-792444 – Fax 353-91-792445
Sampling Interval
The Sampling Interval selects how often the I/O points are
updated. The default is 1 second. The minimum interval
is 0.0000625 (62.5usec) for sampling only one analog input, or 0.005
for all 8 analog inputs. To sample more points, the interval
must be increased, because the analog input gets first priority
and all other reads/writes must be interleaved between
the analog reads. The Sampling Interval is used for display
and for the log file.